Current position:

Product Details

RYFHS-ER-01 Enclosed Emergency Shower and Eyewash Room with Stainless Steel Interior and Floor Grating

Product Overview

The RYFHS-ER-01 is a freestanding enclosed emergency shower and eyewash room: a 900 mm wide, 2400 mm high cabinet with a white frame and branded header, stainless steel wall and ceiling panels inside, a full-height folding curtain door on the front face, and a stainless steel grating floor over a collection base. Inside, a stainless steel riser carries an umbrella shower head at the top and a large eyewash bowl at working height, with a green PUSH plate for the eyewash and a pull rod for the shower. The enclosure is the point of the product: it gives the injured person a screened space to undress and flush in privacy, and it contains the splash, the run-off and the contaminated clothing inside a defined footprint instead of across the walkway.

What an Enclosure Fixes — and What It Creates

An enclosure is often bought as if it were an upgrade to the shower itself. It is not. It changes the human factors around the shower, and it adds three obligations that a bare column does not have.

Findability. A closed booth hides its occupant. Someone who collapses inside will not be seen from the walkway, so the installation needs an occupancy indication — an alarm on activation, a door that cannot self-latch, or a routine check written into the shift round. Without one of these, the privacy benefit turns into a rescue delay.

Escape. The door must open from the inside with no key, no latch and no handle that becomes slippery when wet. A folding curtain that jams on a wet floor, or a swing door that opens inward against a fallen body, is worse than no door at all.

Atmosphere and hygiene. The enclosed volume holds humidity, chemical vapour and contaminated run-off. It needs ventilation and a cleaning routine; a booth that stays damp grows biofilm on the grating and the panels, and the next user is then flushing in contaminated water.

What the enclosure does not fix is the water. Tepid temperature, fifteen minutes of flushing and adequate pressure are still properties of the supply, not of the cabinet.

Key Features

  • Freestanding enclosed room, 900 mm wide by 2400 mm high as marked, with a white frame and a branded header panel.

  • Stainless steel wall and ceiling panels with peel-off protective film, giving a washable interior that will not absorb chemicals.

  • Full-height folding curtain door with vertical slats, opening across the full front face for a wide entry and a clear exit path.

  • Stainless steel grating floor over a collection base, so run-off is caught underfoot rather than spreading outside the booth.

  • Stainless steel 304 umbrella shower head on a stainless riser running the full height of the booth.

  • Large stainless eyewash bowl with twin nozzles under yellow protective covers, fed from the same riser.

  • Green PUSH plate on the eyewash for hands-free activation; pull rod for the shower.

  • Interior dimension visible in the photograph is a working envelope, not a minimum: check head height and bowl height against the standard before fixing the base.

  • Panels and frame are assembled on site, so the unit can be carried through a standard door before erection.

Technical Specifications

ModelRYFHS-ER-01
TypeFreestanding enclosed emergency shower and eyewash room
Overall size900 mm wide x 2400 mm high as marked on the unit; depth per project drawing
EnclosureWhite powder-coated frame with branded header panel; stainless steel wall and ceiling panels with protective film
DoorFull-height folding curtain door with vertical slats across the front face
FloorStainless steel grating over a collection base
Shower head and flowStainless steel 304 umbrella head on stainless riser, minimum 75.7 L/min at 0.2–0.4 MPa
Eyewash bowl and flowLarge stainless bowl with twin nozzles and yellow covers, minimum 11.4 L/min at 0.2–0.4 MPa
ActivationPull rod for the shower; green PUSH plate for the eyewash, both hands-free once operated
Water connectionsInlet and waste at the base, sized to the project; confirm before the base is set
MarkingPUSH plate at the eyewash and identification signage on the header
AssemblyPanels, frame and grating supplied as a knocked-down set for site erection

Installation and Commissioning

  1. Set the collection base level and connect the waste before the panels go on; the base must drain freely and must not rely on the grating to hold water.

  2. Erect the frame and panels on a flat floor, and check that the door track or hinge line is clear of the floor by the clearance the curtain needs when wet.

  3. Connect the inlet, flush the line with the strainer removed, then confirm the shower head sits within the standard head height band and the bowl within the standard bowl height band.

  4. Operate the PUSH plate and the pull rod and confirm both stay open without being held, and that the shower pattern covers the standing position inside the booth.

  5. Run the shower at full flow for several minutes and watch the grating and base: water must not back up over the grating or escape under the frame.

  6. Agree and record the occupancy check — how a person inside is detected — and fit the alarm or signage that the chosen method requires before the unit is released for use.

Operation and Maintenance

Weekly: operate the shower and the eyewash for at least three minutes, and check that the interior drains completely with no standing water under the grating.

Monthly: wipe the panels and the bowl, clear debris from the grating, check that the curtain door runs freely and does not self-latch, and confirm the PUSH plate and pull rod move without sticking.

Quarterly: lift the grating and clean the collection base; inspect panel joints and fixings for corrosion; descale the eyewash nozzles and the shower head face.

Annually: check the structure for movement at the base, verify flow rates against the commissioning record, and review the occupancy check with the site's emergency response team.

Standards and Compliance

The shower and eyewash inside the booth are designed to ANSI Z358.1-2014 figures: 15 minutes of flushing with tepid water at 20–37 °C, hands-free activation, and a location within ten seconds of the hazard. The enclosure itself is not covered by that standard, and it does not relax any of its requirements — head height, bowl height, activation force and unobstructed access must still be verified with the door open and the booth in its installed position. Where the site is in a classified area, the internal fittings, any lighting or alarm and the extraction, if fitted, must be selected for the zone. The run-off collected under the grating is contaminated water and must be routed to drainage permitted by the site's environmental rules, not to open ground.

Applications

Chemical unloading areas, laboratories and pilot plants, battery rooms, plating and pickling lines, and any indoor or covered site where a person needs to remove contaminated clothing before flushing and where splash must be kept inside a defined footprint. It suits locations close to walkways and offices where an open shower column would spray across a traffic route.

Ordering

State the model RYFHS-ER-01, the required depth, the inlet and waste sizes, whether the interior panels are to be stainless steel 304 or 316, and whether lighting, an activation alarm or mechanical extraction is to be included. Confirm the floor level and the drainage point before the collection base is set, and confirm the head and bowl heights against the standard for your jurisdiction. The header branding and the signage language are supplied to order; the unit in the photograph carries Chinese signage and should be specified with the language your site requires.