Short answer: ANSI/ISEA Z358.1-2014 requires plumbed eyewash and shower units to be activated weekly and inspected thoroughly at least annually. The weekly check proves the unit works today; the annual inspection proves it still meets the standard.
The confusion is common: teams either treat the weekly flush as a full inspection, or they skip weekly activation because "the annual service is booked". Both leave a gap that shows up in an audit.
The purpose is twofold - confirm the unit operates, and refresh the stagnant water sitting in the supply leg. A weekly check should record:
The valve opens fully, hands-free, in one second or less
Both eyewash outlets flow evenly, with no sputtering or blocked nozzles
Flow continues for the full test period without dropping
The fluid runs clear, with no rust, sediment or odour
Drainage carries the water away without pooling at the base
Two minutes of flow is a practical weekly test. It is not the 15-minute compliance duration - that is a design requirement, not a weekly test.
The annual inspection is a condition assessment, not just a functional test. It typically covers:
| Area | What is checked |
|---|---|
| Flow performance | Measured flow rate and spray pattern height against the 33-53 inch band |
| Fluid temperature | Measured at the outlet, within the 60-100 F tepid range |
| Valve and actuator | Opening time, stay-open function, corrosion, ease of operation |
| Piping and strainers | Blockages, scale, damaged seals, signs of freezing |
| Signage and access | Visibility of the unit, unobstructed path, lighting |
| Documentation | Log continuity, corrective actions closed out |
In our experience supplying units to chemical, petroleum and laboratory sites, three failures repeat:
1. No outlet temperature record. The weekly flush is logged, but nobody measures the water temperature. A unit fed from an unlagged line can sit well below 60 F in winter and still pass a visual check.
2. The log is a tick box. A sheet with seven identical ticks and one signature tells an auditor nothing. Record the flow observation and any deviation, even when the deviation is minor.
3. The path is blocked. Palletised stock, a parked forklift or a new racking line can silently break the 10-second access rule. This is an inspection item, not a housekeeping issue.
It is not covered by the plumbed weekly requirement in the same way, but it needs more frequent attention: the tank must be drained, cleaned and refilled on the manufacturer's schedule, and the preservative checked. Treat it monthly at minimum.
A trained employee on site is sufficient. The annual inspection is better handled by someone competent to measure flow and temperature and to judge pipework condition.
You have an evidence gap, not necessarily an equipment fault. Re-test immediately, document the corrective action and the reason for the gap, and close it out in the same log. Auditors accept a documented recovery; they do not accept a back-filled sheet.
No. Weekly activation is a functional check. The annual inspection adds measurement, condition assessment and documentation review.
The most common reason weekly activation lapses is that the unit is inconvenient to test - a high wall mount, a pedal that needs two people, or a drain that floods the walkway. That is a specification problem disguised as a discipline problem.
If your team is fighting the equipment to test it, the equipment is wrong for the location. Our eyewash station range includes low-level foot-pedal pedestal units and wall-mounted models with stay-open valves, so a single person can run the weekly test in under a minute.
Sources: ANSI/ISEA Z358.1-2014 weekly activation and annual inspection requirements; CCOHS emergency shower and eyewash guidance.